  • XCGIRNS(Safe)-12气体全绝缘环网开关设备(ABB).webp

XCGIRNS(Safe)-12 gas fully insulated ring network switchgear (ABB)

XCGIRNS(Safe) series switch cabinet is a gas fully insulated compact ring network cabinet jointly produced by combining ABB's core technology and our company's many years of manufacturing experience. The product adopts modular design and can realize the perfect unity of common box unit and extended unit (independent gas box) according to any combination of different design schemes. It is not only suitable for the requirements of network nodes or user terminals, but also meets the flexible application requirements of various secondary substations for compact switch cabinets.
The core element of XCGIRNS series switchgear adopts the new SF6 gas insulated medium voltage switchgear-Safe series switch developed by ABB. The Safe series switch is a completely sealed system with all live parts and switches enclosed in a stainless steel housing. The entire switching device is not affected by external environmental conditions, so that operational reliability and personal safety can be ensured, and maintenance-free is realized. By selecting the expandable bus bar, any combination can be realized to achieve safe modularization. Safe series switches can also provide factory automation solutions, forming the concept of intelligent switches, and on-site installation and commissioning workload to a minimum.
XCGIRNS(Safe) series products have passed the type test certification of the national high-voltage electrical test center, and can be widely used in small secondary power distribution stations, box-type switching stations, working conditions, airports, railways, commercial areas, high-rise buildings, highways, Subway and other places with harsh natural conditions.


  • Product Description
  • Technical features
  • Main technical parameters
    • Commodity name: XCGIRNS(Safe)-12 gas fully insulated ring network switchgear (ABB)

    XCGIRNS(Safe) series switch cabinet is a gas fully insulated compact ring network cabinet jointly produced by combining ABB's core technology and our company's many years of manufacturing experience. The product adopts modular design and can realize the perfect unity of common box unit and extended unit (independent gas box) according to any combination of different design schemes. It is not only suitable for the requirements of network nodes or user terminals, but also meets the flexible application requirements of various secondary substations for compact switch cabinets.
    The core element of XCGIRNS series switchgear adopts the new SF6 gas insulated medium voltage switchgear-Safe series switch developed by ABB. The Safe series switch is a completely sealed system with all live parts and switches enclosed in a stainless steel housing. The entire switching device is not affected by external environmental conditions, so that operational reliability and personal safety can be ensured, and maintenance-free is realized. By selecting the expandable bus bar, any combination can be realized to achieve safe modularization. Safe series switches can also provide factory automation solutions, forming the concept of intelligent switches, and on-site installation and commissioning workload to a minimum.
    XCGIRNS(Safe) series products have passed the type test certification of the national high-voltage electrical test center, and can be widely used in small secondary power distribution stations, box-type switching stations, working conditions, airports, railways, commercial areas, high-rise buildings, highways, Subway and other places with harsh natural conditions.

  • 1) Unity

    The co-box unit and the extended unit are perfectly unified. In order to meet the market demand, XCGlRNS(Safe) series switch cabinet of the common box unit and expansion unit adopts a common technology platform, so that the common box unit is integrated into a subset of the expansion unit, reducing the complexity of the product.
     

    2) Flexible expansion

    XCGlRNS(Safe) co-box unit is 2, 3, 4, 5 or 6-way standard configuration, and other equipment is attached according to customer requirements. The common box unit can be configured with up to 6 modules in the same SF6 insulated gas chamber, which can provide 16 combinations for the power distribution network and adapt to most occasions where ring network units are needed.
    The expansion unit (independent gas box) has extremely special flexibility due to its combination of full module and half module and its own scalability. The extended unit can be configured with up to 6 modules in the same SF6 insulated gas chamber. When the number of modules is more than 6, the switch cabinet needs to be connected by top extension bus to realize semi-modular structure, and the full module configuration can also be realized by using extension bus between all modules. Through the combination of 9 different functional modules, a power distribution scheme from simple to complex can be formed to meet the various configuration requirements of secondary substations and switching stations.
     

    3) Compact structure

    Except for the circuit breaker CB cabinet and the air-insulated metering cabinet, all modules are only 325mm wide and the metering cabinet width is 696mm;CB cabinet has three widths: 446/500/696mm. The cable connection sleeves of all units have the same height to the ground, which is convenient for on-site construction.
     

    4) Complete protection function

    XCGlRNS(Safe) design provides two options for the protection of the transformer: load switch fuse combination and circuit breaker with relay protection. The load switch fuse combination is used for transformers of 160OkVA and below, while the circuit breaker with relay protection can be used for transformer protection of various capacities. At the same time, the design of XCGIRNS(Safe) also provides two options for circuit breakers for line protection: both circuit breakers are VG series vacuum circuit breakers and are sealed in SF6 boxes. The rated current of the V module is 630A, and the rated current of the CB module can reach 1250A.

    5) Maintenance-free
    All high-voltage live parts are located in the stainless steel box body, and the box shell is sealed and welded with stainless steel. The protection level is IP67, even if the fuse chamber is used, it has IP67 protection level. It can be installed in wet, sandy, dusty, salt, mines, box-type substations and any places where surface pollution flashover is easily caused by air pollution without taking special precautions. The extended bus is fully insulated and shielded to ensure that it is not affected by changes in the external environment and is maintenance-free, without bus cleaning and anti-small animals.

    6) High reliability
    All live parts are enclosed in SF6 gas chamber. The switch has a reliable pressure relief channel. It has passed the internal arcing test of 20kA/ls. The load and grounding switches are three-position switches, which simplifies the interlock between each other. There is a reliable mechanical interlock between the cable chamber cover plate and the load switch, and the incoming unit can be equipped with an arc extinguisher. Selecting this function can meet the needs of internal arc suppression, at this time, the switch may not be provided with SF6 pressure relief channel.
     

  •   Module C Module F V module CB module
      Load switch Combined electrical appliances Vacuum circuit breaker Isolating/earthing switch Vacuum circuit breaker Isolating/earthing switch
    Rated voltage kV 12 12 12 12 12 12
    Power frequency withstand voltage kV 42 42 42 42 42 42
    Lightning impulse withstand voltage kV 75 75 75 75 75 75
    Rated current A 630 Note D 630   1250/800  
    Breaking capacity:
    Closed-loop breaking current A 630          
    Cable charging breaking current A 135          
    5% rated active load breaking current A 31.5          
    Ground fault breaking current A 200          
    Breaking current A for cable charging in case of earth fault 115          
    Short-circuit breaking current kA   Note 2) 20 or 25   25  
    closing capacity kA 63 Note 2) 50 or 63 50/40 63 63
    Short-time withstand current 4 seconds kA 25   25      
    Mechanical life times 5000 3000 5000 3000 10000 3000

     

    XCGIRNS (Safe)-CB series technical parameters

    Switch cabinet model   XCGIRNS(Safe)-CB XCGIRNS(Safe) -CB/B XCGIRNS(Safe)-CBZE
    Rated voltage (kV)   12    
    Rated current (A)   800/1250 800 1250
    Breaking current of tremuline (kA)   25 25/20 25
    Insulation level (kV) Power frequency 42    
    (interphase/fracture) Pulse 75    
    Power frequency short-time tolerance (kA/s)   25/4    
    Peak tolerance (kA)   63    
    Number of breaker operations   10,000    
    Rated operation sequence of circuit breaker   0-0.3 s-CO-3 min-CO    
    Number of three-position switch operations (disconnector/earthing switch) 3,000/3,000    
    Breaker energy storage mode   Electric manual    
    Circuit breaker operation mode   Electric manual    
    Three-position switch operation mode   Manual   Electric
    Electric operating mechanism motor operating voltage 48 V DC1110/220 V DC/AC  
    Closing and opening coil voltage   24/30/48/110/220 V DC   48/110/220 V DC
    Interlocking mode of circuit breaker and three-position switch Mechanical   Relay control
    Switch cabinet inline interlock   Mechanical   Relay control
    relay protection   Normal, optional   Optional
    Access line mode   Front, lower in/out pre-assembled cable head Front and rear, lower in/out; the rear can also be selected as upper in/out or with PT. Front, lower in/out. Pre-assembled cable head.
    Cabinet size (mm) Width (W) 446        696 500 696
      High (H) 1806 2000/2500 (clear height/including arc guide cover) 1806
      Deep (D) 820 500/1800 (with PT) 820
    Current transformer   ring, mounted on cable Annular, mounted on cable. CT installed in the rear outlet casing is optional. ring, mounted on cable
    Connect with other Safe units   External busbar Not available External busbar
    Installation method   against the wall Middle part of transformer room against the wall
    Internal Arcing Tolerance Class   AFL AFLR AFL
    Protection grade of cabinet body   IP3X (IP4X optional) IP4X (optional IP5X) IP3X
    Protection grade of primary part   IP67    
    Rated charging pressure of air tank (abs) 0.14 MPa    
    Bus bar between cabinets   External, solid insulation can be touched, there is a closed busbar room.  
    Embedded current of external busbar between cabinets   1250 A  

Recommended Products