XCFKRN12 air pressure type load switch and combination electric appliance

XCFKN series air pressure load switch and its combined electrical appliances produced by Xiancheng Technology Co., Ltd. are designed and developed by our company by digesting and absorbing foreign advanced technology and improving it in combination with the requirements of users in our country. Is suitable for urban power grid transformation and construction needs of a new generation of high-voltage electrical products. The performance conforms to GB/T 3804-2004 "3.6kV ~ 40.5kV high voltage AC load switch" and GB/T 16926-2009 "high voltage AC load switch-fuse combination appliance" and other relevant standards. China National High Voltage Electrical Apparatus Quality Supervision and Inspection Center is entrusted to carry out comprehensive type test according to the latest national standards. The main technical parameters of the product are already at the leading level of similar products in China. This product is widely used in factories, schools, residential areas, high-rise buildings and other three-phase AC, system voltage 10kV, rated frequency 50Hz distribution system, as the acceptance and distribution of electrical energy, can be used for ring network switchgear, box-type substation, and other power distribution equipment.


  • Product Description
  • Technical features
  • Main technical parameters
    • Commodity name: XCFKRN12 air pressure type load switch and combination electric appliance

    XCFKN series air pressure load switch and its combined electrical appliances produced by Xiancheng Technology Co., Ltd. are designed and developed by our company by digesting and absorbing foreign advanced technology and improving it in combination with the requirements of users in our country. Is suitable for urban power grid transformation and construction needs of a new generation of high-voltage electrical products. The performance conforms to GB/T 3804-2004 "3.6kV ~ 40.5kV high voltage AC load switch" and GB/T 16926-2009 "high voltage AC load switch-fuse combination appliance" and other relevant standards. China National High Voltage Electrical Apparatus Quality Supervision and Inspection Center is entrusted to carry out comprehensive type test according to the latest national standards. The main technical parameters of the product are already at the leading level of similar products in China. This product is widely used in factories, schools, residential areas, high-rise buildings and other three-phase AC, system voltage 10kV, rated frequency 50Hz distribution system, as the acceptance and distribution of electrical energy, can be used for ring network switchgear, box-type substation, and other power distribution equipment.

    • The load switch is of frame structure with compact structure. Integrated load switch, fuse, grounding switch as one of the high-performance high-voltage electrical products.
    • When the brake is opened, it has obvious isolation fracture, which increases the inner diameter of the compressed air and enhances the arc extinguishing ability compared with similar products, so it has a strong breaking ability.
    • There is a mechanical interlock between the load switch and the grounding switch to prevent misoperation.
    • There is a transparent cover to close the live static contact (busbar room), and it is absolutely safe to repair or replace the fuse.
    • The load switch is equipped with a door lock, which can easily interlock the switch cabinet door with the switch. When the cabinet door is opened or the door lock is unlocked, the load switch cannot be operated. When the grounding switch is not closed, the cabinet door cannot be opened.
  • Serial Number Name Unit Load switch XCFKN12-12(D)/T630-20 Combined electrical XCFKRN12-12(D)/T 100-31.5
    1 Rated voltage kV 12
    2 Rated frequency Hz 50
    3 Rated current A 630 100
    4 Rated short-time withstand current I/O 20/3  
    5 Rated peak withstand current kA 50  
    6 Rated short-circuit closing current kA 50 80
    7 Rated active load breaking current A 630  
    8 Rated closed-loop breaking current A 630  
    9 No-load transformer breaking kVA   1600
    10 Rated cable charging current A 10 10
    11 Rated short-circuit breaking current kA   31.5
    12 Rated transfer current A   1200
    13 Trigger opening time of impactor S   N 0.05
    14 Power frequency withstand voltage (Imin) KV Interphase, opposite ground: 42, isolation fracture: 48
    15 Lightning impulse withstand voltage KV Interphase, relative ground: 75, isolation fracture: 85 (peak value)
    16 Mechanical life Times 5000

     