MLS Advanced Low Voltage Drawer Switch Cabinet
MLS-type withdrawable low-voltage switchgear is a low-voltage switchgear designed and produced by our company with the introduction of foreign advanced technology, while MLSD-type fixed and separated low-voltage switchgear is a fixed and separated low-voltage switchgear with domestic advanced level developed on the basis of MLS according to the particularity and applicability of power distribution scheme. MLS/MLSD adopts advanced design concept and manufacturing technology, and has the characteristics of safety, reliability, economy and environmental protection. It is suitable for power supply systems with rated working voltage of 690V and below 50~60HZ. Such as: power plants, substations, industrial and mining enterprises, buildings, residential, transportation, etc. as power distribution, motor and electrical equipment control, lighting, power conversion, power compensation.
- Product Description
- Technical features
- Main technical parameters
-
- Commodity name: MLS Advanced Low Voltage Drawer Switch Cabinet
MLS-type withdrawable low-voltage switchgear is a low-voltage switchgear designed and produced by our company with the introduction of foreign advanced technology, while MLSD-type fixed and separated low-voltage switchgear is a fixed and separated low-voltage switchgear with domestic advanced level developed on the basis of MLS according to the particularity and applicability of power distribution scheme. MLS/MLSD adopts advanced design concept and manufacturing technology, and has the characteristics of safety, reliability, economy and environmental protection. It is suitable for power supply systems with rated working voltage of 690V and below 50~60HZ. Such as: power plants, substations, industrial and mining enterprises, buildings, residential, transportation, etc. as power distribution, motor and electrical equipment control, lighting, power conversion, power compensation.
-
The frame structure used is highly flexible, and once the structure is assembled, maintenance is no longer required. Different standard components can be installed in the cabinet to meet various requirements. The design of the system and the materials used can prevent the occurrence of fault arc to the greatest extent. Once a fault occurs, the arc can be extinguished in a short time.
-
Rated insulation voltage of main circuit AC 660V, 1000V Rated operating voltage of main circuit AC 380V, 660V Rated frequency 50Hz/60Hz
Rated operating current of busbar
Horizontal bus (main bus)
630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000 and 6300 after the horizontal bus is installed in the cabinet
The horizontal bus is placed on the top of the cabinet: 630, 800. 1000. 1250. 1600. 2000, 2500, 3200, 4000 and 6300
Vertical bus (branch bus)
L-type vertical bus: 1200, 2000A
Rectangular vertical bus: 630-1600A (only for horizontal bus on cabinet top)
Rated short-time withstand current (IS)
Horizontal bus (main bus):50, 80kA
Vertical bus (branch bus):50kA
Protective conductor (grounding main bus):30, 48kA
Neutral bus (neutral main bus):30, 48kA
Rated peak withstand current
Horizontal bus (main bus):105, 176kA
Vertical bus (branch bus):105kA
Protection level
IP4X、IP3X