  • VES1一体化真空断路器(1708593049684).webp

VES1 integrated vacuum circuit breaker

VES1 integrated high-voltage vacuum circuit breaker and its supporting M-XGN-type miniaturized switchgear are a new generation of miniaturized power distribution products introduced by Xicheng Technology Co., Ltd. The product has strong versatility in structure and can be easily used for well cabinet with XGN mouth switch cabinet (equipped with FLN36(SF6), FKN12, FZN25G, GN19 and other switches). The minimum size of the product cabinet can reach 500mm wide, which is nearly 40% less than that of XGN port switch cabinet composed of traditional VS1 vacuum circuit breaker, thus greatly reducing the space occupied by equipment and saving investment cost.

VES1 integrated high-voltage vacuum circuit breaker is an integrated product integrating isolating switch, vacuum circuit breaker and grounding switch (optional). The product adopts modular mechanism and has the characteristics of simple structure, reliable performance, compact structure and small size. The product is suitable for the use of ring network power supply unit, power plant and substation, especially for the working condition of enterprises, buildings, high-rise buildings and other fields. Installed in substations, box-type substations and switches and other complete sets of equipment products, can easily meet the automatic requirements of power distribution.


  • Product Description
  • Technical features
  • Main technical parameters
    • Commodity name: VES1 integrated vacuum circuit breaker

    VES1 integrated high-voltage vacuum circuit breaker and its supporting M-XGN-type miniaturized switchgear are a new generation of miniaturized power distribution products introduced by Xicheng Technology Co., Ltd. The product has strong versatility in structure and can be easily used for well cabinet with XGN mouth switch cabinet (equipped with FLN36(SF6), FKN12, FZN25G, GN19 and other switches). The minimum size of the product cabinet can reach 500mm wide, which is nearly 40% less than that of XGN port switch cabinet composed of traditional VS1 vacuum circuit breaker, thus greatly reducing the space occupied by equipment and saving investment cost.

    VES1 integrated high-voltage vacuum circuit breaker is an integrated product integrating isolating switch, vacuum circuit breaker and grounding switch (optional). The product adopts modular mechanism and has the characteristics of simple structure, reliable performance, compact structure and small size. The product is suitable for the use of ring network power supply unit, power plant and substation, especially for the working condition of enterprises, buildings, high-rise buildings and other fields. Installed in substations, box-type substations and switches and other complete sets of equipment products, can easily meet the automatic requirements of power distribution.

  • Functional composite, integrated products
    VES1 integrated high-voltage vacuum circuit breaker is an integrated product integrating isolating switch, vacuum circuit breaker and grounding switch (optional). Its isolating switch has obvious visible isolating fracture, which ensures the safety of operators. Reliable mechanical interlocking shall be provided among the isolating switch, circuit breaker and earthing switch. The isolating switch and earthing switch adopt linkage operating mechanism, that is, when the isolating switch is closed, the earthing switch is opened, and vice versa.

    Modular spring energy storage operating mechanism
    The VES1 integrated high-voltage vacuum circuit breaker adopts a modular operating mechanism. The mechanism and the switch body are independent of each other. The operating mechanism can be inserted or withdrawn as a whole. It has the characteristics of small operating power, simple structure, stability and reliability, and easy maintenance.
    Day 2.3 compact structure, small
    The product has a compact structure, and the minimum size of the cabinet can reach 500mm wide. It can be easily combined with switch cabinets composed of FLN36(SF6), FKN12, FZN25G, GN19, etc.

    Perfect mechanical interlocking

    • The circuit breaker and the isolating switch are provided with perfect mechanical interlocking function in the yellow operating mechanism: when the cabinet door is opened, the isolating circuit breaker cannot be operated;
    • Only when the isolating switch is closed, the circuit breaker can be closed;
    • After the circuit breaker is closed, the isolation/grounding switch cannot be operated;
    • The cabinet door can only be opened when the isolating/grounding switch is in the isolating/grounding position;
    • All interlocking functions have been designed inside the switch elastic yellow operating mechanism. Only one lock piece needs to be installed on the switch cabinet, and complicated interlocking design is no longer required, which is very convenient to use.
  • Technical data for circuit breakers

    Serial Number Project Unit Data
    1 Rated voltage kV 12
    2 Rated insulation level Imin power frequency withstand voltage: phase-to-phase, relative to ground/isolation fracture 42/48
    Lightning impulse withstand voltage: phase-to-phase, relative to ground/isolation fracture 75/85
    3 Rated frequency Hz 50
    4 Rated current A 630 1250
    5 Rated short-circuit breaking current   20 25 31.5
    6 Rated short-time withstand current 20 25 31.5
    7 Rated short-circuit closing current (peak) kA 50 63 80
    8 Rated peak withstand current 50 63 80
    9 Rated out-of-phase grounding fault breaking current 17.3 21.7 27.4
    10 Rated short circuit duration (main circuit) S 4
    11 Rated operating sequence   O-03s-CO-180s-CO
    12 Mechanical life Times 10000

     

    Adjusted mechanical characteristic parameters of circuit breaker

    Serial Number Project Unit Data
    1 Contact opening distance mm 9± 1
    2 Overtravel 3.5±1
    3 Three-phase opening and closing different ms ≤2
    4 Average gate speed m/s 0.9~1.4
    5 Average closing speed 0.4 ~ 0.8
    6 Closing time ms ≤ IOO
    7 Opening time 35~60
    8 Main circuit resistance of each phase of circuit breaker μ Q ≤40
    9 Resistance of each phase main circuit of isolating circuit breaker μ∩ ≤ 80
    10 Isolating switch three-phase different periods mm ≤ 2
    11 Allowable cumulative wear thickness of moving and static contacts mm 3

     

    Technical parameters of release and locking electromagnet

    Equipment Name Rated voltage (V) Rated current (A)
    Opening trip TQ DC220/110 1/2
    Closing trip HQ DC220/110 0.77/0.55
    Overcurrent release Y7, Y8, Y9   5A
    Locking electromagnet YI DC220/110  

     

    Technical parameters of energy storage motor

    Rated voltage Power (W) Energy storage time (S) Applicable current level
    AC/DC220/110 90 ≤ 15 20kA、25kA、31.5kA