ZYN □-12kV armored longitudinal removal type indoor AC metal enclosed switchgear
ZYN port-12kV armored longitudinal removal type indoor AC metal enclosed switchgear (hereinafter referred to as longitudinal intermediate cabinet) is a new generation of air insulated switchgear independently developed by our company. Its matching longitudinal removal type isolating vacuum circuit breaker is also independently developed by our company. It is a new product integrating the functions of isolating switch and vacuum circuit breaker (hereinafter referred to as longitudinal removal type isolating circuit breaker). The main circuit of the longitudinal central cabinet adopts the vertical arrangement of the main primary components directly connected from top to bottom, so that the main circuit does not need branch bus transition and other insulation supports, the structure is simple and compact, and the separation and closing state of the double isolation fracture is directly visible, which is our patented product.
The longitudinal middle cabinet is mainly composed of fixed cabinet body and extractable parts. According to the function of electrical equipment in the cabinet, the cabinet body is divided into four different functional units with metal partition: bus room, circuit breaker room, cable room and instrument room, and each functional compartment is provided with pressure relief channel. At the same time, a small bus room on the top of the cabinet is added for convenience of construction. The cabinet shell and the partitions of each functional unit are made of aluminum-zinc plate or cold-rolled steel plate and bolted after bending. The installation and debugging can be carried out in front of the cabinet and behind the cabinet at the same time. If the circuit breaker needs to be overhauled and replaced, the switch replacement can be completed in a short time by pulling out the longitudinal removal type isolating circuit breaker handcart, thus saving time and maintenance cost. Compared with similar products, this product has a functional composite. Small size, light weight, convenient maintenance and safety and environmental protection.
- Product Description
- Technical features
- Main technical parameters
-
- Commodity name: ZYN □-12kV armored longitudinal removal type indoor AC metal enclosed switchgear
ZYN port-12kV armored longitudinal removal type indoor AC metal enclosed switchgear (hereinafter referred to as longitudinal intermediate cabinet) is a new generation of air insulated switchgear independently developed by our company. Its matching longitudinal removal type isolating vacuum circuit breaker is also independently developed by our company. It is a new product integrating the functions of isolating switch and vacuum circuit breaker (hereinafter referred to as longitudinal removal type isolating circuit breaker). The main circuit of the longitudinal central cabinet adopts the vertical arrangement of the main primary components directly connected from top to bottom, so that the main circuit does not need branch bus transition and other insulation supports, the structure is simple and compact, and the separation and closing state of the double isolation fracture is directly visible, which is our patented product.
The longitudinal middle cabinet is mainly composed of fixed cabinet body and extractable parts. According to the function of electrical equipment in the cabinet, the cabinet body is divided into four different functional units with metal partition: bus room, circuit breaker room, cable room and instrument room, and each functional compartment is provided with pressure relief channel. At the same time, a small bus room on the top of the cabinet is added for convenience of construction. The cabinet shell and the partitions of each functional unit are made of aluminum-zinc plate or cold-rolled steel plate and bolted after bending. The installation and debugging can be carried out in front of the cabinet and behind the cabinet at the same time. If the circuit breaker needs to be overhauled and replaced, the switch replacement can be completed in a short time by pulling out the longitudinal removal type isolating circuit breaker handcart, thus saving time and maintenance cost. Compared with similar products, this product has a functional composite. Small size, light weight, convenient maintenance and safety and environmental protection.
-
ZWV port -12 series longitudinal removal type isolation vacuum circuit breaker is a new generation of miniaturized vacuum circuit breaker. Lower isolating switch, vacuum circuit breaker and interlocking mechanism in one functional composite circuit breaker. The product is compact in structure, small in size, and has the characteristics of removable and double-isolated direct-acting modules. The product is widely used in 3-12kV three-phase AC 50Hz power system.
-
ZYN□-12kV Switchgear Technical Parameters
Serial Number Project Unit Parameters 1 Rated voltage kV 12 2 Rated frequency Hz 50 3 Rated insulation level Imin power frequency withstand voltage (effective value) kV Interphase, relatively Isolation fracture 42 48 Lightning impulse withstand voltage (peak) 75 85 Auxiliary control circuit Imin power frequency withstand voltage V 2000 4 Rated current of main bus A 630、1250 5 Rated current of branch bus A 630、1250 6 Rated short-circuit breaking current kA 25, 31.5 7 Rated short-circuit closing current (peak) 63, 80 8 Rated short-time withstand current (4S) 25, 31.5 9 Rated peak withstand current 63, 80 10 Rated voltage of auxiliary control circuit V DC110/220, AC220 11 Protection level Enclosure IP4X compartment, IP2X when circuit breaker door is open 12 Loss of operation continuity level LSC2B 13 IAC Level AFLR, 31.5kA∕0.5s 14 Overall dimension of middle cabinet (width X depth X height) mm 475 × 1300X2200 15 Total kg 1000 Technical Parameters of ZYV Port -12 Circuit Breaker
Serial Number Project Unit Numerical 1 Rated voltage kV 12 2 Rated short-time power frequency withstand voltage (Imin) 42 3 Rated lightning impulse withstand voltage 75 4 Rated frequency Hz 50 5 Rated current A 630、1250 6 Rated short-circuit breaking current kA 20 25 31.5 7 Rated short-circuit closing current (peak) 50 63 80 8 Rated short-time withstand current 20 25 31.5 9 Rated peak withstand current 50 63 80 10 Rated short-circuit breaking times Times 30 11 Rated short circuit duration S 4 12 Rated out-of-phase grounding fault breaking current kA 17.3 21.7 27.4 13 Rated operating sequence One 0.3S-one 18OS-one 14 Main circuit resistance of each phase of circuit breaker μΩ ≤40 15 Resistance of each phase main circuit of isolating circuit breaker μΩ ≤60